OW5H-A 5-Digit Analog Input Display / Control Table
The OW5H-A is a high-precision five-digit analog input display controller that integrates multiple sensor inputs, alarm control, analog output, and communication functions, suitable for various industrial field measurement and process monitoring needs. The product uses a high-brightness LED display, providing clear and easy-to-read values, and can be flexibly configured according to application requirements, offering stable and reliable measurement and control performance.

Product Introduction
The OWH-A supports a variety of commonly used industrial input signals, including RTD, resistor, potentiometer, voltage, current and 4–20mA, etc. The display range can be set from -99999 to 99999, and the unit and decimal point position can be freely adjusted.
Built-in multi-segment alarm output, can be used with relay to control external devices, and can be equipped with analog output and RS-485 communication for easy integration into automation control systems or upper-level monitoring platforms. It is widely used in process monitoring, equipment measurement and industrial control fields.
Features
- Accuracy: ± 0.1% full scale ± 1 decimal place (DC/PT-100/potential meter/resistor/load cell); ± 0.2% full scale ± 1 decimal place (AC).
- It can measure AC/DC current, AC/DC voltage, potentiometers, transmitters, temperature, load cells, resistance, and other signals.
- Display range: -19999 ~ 99999, decimal point can be arbitrarily set.
- When the maximum rated value is entered, the display range can be adjusted according to usage needs.
- It can automatically reset and hold (normal or maximum value) 2-4 level alarms (high and low alarms can be set by the user).
- Analog output (15-bit resolution) and digital communication (RS-485 interface) are optional functions and can be used simultaneously.
- High stability, flame-retardant PC casing, high safety.
Selected model/specification: OW5H-A-Code 1-Code 2-Code 3-Code 4-Code
| Code 1 | Input Types |
|---|---|
| D | DC signal |
| A | Average value of communication |
| M | Effective value of communication |
| P | 3-wire potentiometer |
| I | 2-wire resistance meter |
| T | Temperature (PT100) |
| L | Load element |
| 2 | 2/3 line transmitter |
| 4 | 4-line transmitter |
| Code 3 | Working Power Supply |
|---|---|
| A | AC/DC 100-240V |
| D | AC/DC 22V-60V |
| O | Option |
| Code 4 | Alarm Function |
|---|---|
| N | None |
| R2 | 2 sets of Relay alarms |
| R3 | 3 sets of Relay alarms |
| R4 | 4 sets of Relay alarms |
| O2 | 2 sets of OC alarms |
| O3 | 3 sets of OC alarms |
| O4 | 4 sets of OC alarms |
| Code 5 | Analog Output |
|---|---|
| N | None |
| A | 4-20mA |
| V | 0-10V |
| L | LOOP 4-20mA |
| O | Option |
| Code 6 | RS-485 |
|---|---|
| N | None |
| Y | Yes |
| Code 2 | Voltage (V) | Code 2 | Current (A) | Code 2 | 3-Wire Potentiometer |
|---|---|---|---|---|---|
| V1 | 0-50mV | A1 | 0-20uA | P1 | 500Ω-10KΩ |
| V2 | 0-5V | A2 | 0-200uA | P2 | 10KΩ-100KΩ |
| V3 | 1-5V | A3 | 0-2mA | P3 | 100KΩ-1MΩ |
| V4 | 0-10V | A4 | 0-20mA | PO | Option |
| V5 | 0-36V | A5 | 0-200mA | ||
| V6 | 0-300V | A6 | 4-20mA | ||
| V7 | 0-600V | A7 | 0-2A | ||
| VO | Option | A8 | 0-5A | ||
| - | A9 | 0-10A | |||
| - | AO | Option |
| Code 2 | 2-Wire Resistance Meter | Code 2 | Temperature (PT100) | Code 2 | Load Element |
|---|---|---|---|---|---|
| I1 | 0-10Ω | T1 | -50-50°C | L1 | 1mV/V EX.5V |
| I2 | 0-100Ω | T2 | -100-100°C | L2 | 2mV/V EX.5V |
| I3 | 0-1KΩ | T3 | -200-200°C | L3 | 3mV/V EX.5V |
| I4 | 0-10KΩ | T4 | 0-600°C | L4 | 1mV/V EX.10V |
| I5 | 0-100KΩ | TO | Option | L5 | 2mV/V EX.10V |
| IO | Option | L6 | 3mV/V EX.10V | ||
| - | LO | Option | |||
| - | |||||
| - | |||||
| - |
- Note 1: The 2-wire transmitter specification has a built-in 24Vdc excitation power supply, suitable for 2-wire (loop power) transmitters such as pressure, temperature, and humidity transmitters, and can be directly wired for use.
- Note 2: The 3- or 4-wire transmitter specifications provide a 24Vdc excitation power supply, suitable for 3- or 4-wire transmitters such as pressure, temperature, and humidity transmitters, and can be directly wired for use.
- Note 3: Two 5Vdc excitation power supplies for the load cell can be connected in parallel, while a 10Vdc excitation power supply is for single-cell use only.
- Note 4: For alarms with 3 or more relays, only A (NO.) contact output is provided.
- Note 5: The OC alarm provides output from the CE pin of the optocoupler NPN.
Specifications And Characteristics
- Accuracy: ±0.1% full scale ±1 decimal place (DC/potential meter/resistor/PT100/load cell); ±0.2% full scale ±1 decimal place (AC).
- Display screen: High-brightness red LED, character height 10.16mm (0.4”).
- Sampling time: 16 cycles/sec.
- Display range: -19999~99999
- Zero value adjustment range: -19999~99999
- Overload display: doFL / ioFL or -doFL / -ioFL
- Polarity display: Displays "-" when the input signal is reversed.
- Parameter setting method: Key input setting.
- Data storage method: E² PROM memory.
- Alarm action direction: "≥ (Hi) action" or "< (Lo) action" can be set.
- Alarm delay time: User-configurable (0-99 seconds).
- Relay contact capacity: AC 277V/7A, DC 30V/7A
- Analog output resolution: 15-bit digital to analog.
- Analog output response time: <250ms (0-90%).
- Analog output driving capability: Voltage output <20mA, Current output <10V 10V>
- Communication method and protocol: RS-485 Modbus RTU mode.
- Communication transmission rate: 19200/9600/4800/2400 BRPMS (selectable).
- Temperature coefficient: 100ppm/°C (0-60°C).
- Operating environment temperature and humidity: 0-60°C, 20-90%RH (non-condensing).
- Storage environment temperature and humidity: -10-70°C, 20-90%RH (non-condensing).
- Operating power supply: AC/DC 100-240V; AC/DC 22-60V
- Power consumption: <8.5VA (full-function output).
- Insulation withstand voltage: 1.5 kVac/1 min (input/power supply).
- Input impedance:
- Voltage: >2V: 20KΩ/V; ≤2V: 200MΩ
- Current: ≥0.2A: 100mV (terminal voltage drop); <0.2A: 1V (terminal voltage drop).


Wiring Diagram