OWT-TR Signal Isolation Converter (17.5mm)
The OWT series converters/distributors are primarily designed for conversion and isolation in general signal loops, such as 4~20mA, 0~10V, RTD-PT100Ω, and AC voltage/current signals, with a complete range of models available. This slim converter/distributor provides two signal outputs (isolated between outputs) or a 24V excitation power supply for the transmitter. The switchable power supply also facilitates installation. Power, input, and output indicator lights and pluggable terminal blocks are located on the top for easy on-site installation and monitoring of operating status.

Features
- Optional DIP switch available for switching between six standard output signals: 0-5V/0~10V/1~5V/2~10V/4~20mA/0~20mA.
- Dual-loop outputs are fully isolated, allowing selection of different signals.
- Power, input, and output LED indicators are included for easy monitoring of on-site operating status.
- The specification selection table allows you to specify a precision of 0.1%.
- 17.5mm thin 35mm guide rail mounting.
- Designed in accordance with CE international standards and specifications.
Functional Specifications
OWT-TR(PT100Ω)
| Input Signal | Input Range (selected via a toggle switch on the PCB) |
Input Impedance | ||
|---|---|---|---|---|
| PT100Ω (DIN) |
P1 | 0-50/100/200/400°C | Selected by Dip-Switch | 1MΩ |
| P2 | 0-200/400/600/800°C | |||
| P3 | -50-50/100/200/400°C | |||
| Standard products: Please specify the input signal range in the specification selection table when ordering. | ||||
Accuracy
≤ ±0.2% of F.S.(as specified by the customer when ordering)
≤ ±0.1% of F.S.(optional specification)
≤ ±2% of F.S.(after selection via toggle switch)
Model Specifications
OWT-TR-Output Circuit-Input Range-Output Signal 1/Output Signal 2-Operating Power Supply-(Optional Function)
| CODE | Output Circuit |
|---|---|
| 1 | 1 set of outputs |
| 2 | 2 set of outputs |
| CODE | Input Temperature Range |
|---|---|
| A | -50-+50°C |
| B | 0-50°C |
| C | 0-100°C |
| D | 0-2400°C |
| E | 0-400°C |
| P1 | Dial switch 0-50/100/200/400°C |
| P2 | Dial switch 0-200/400/600/800°C |
| CODE | Input Temperature Range |
|---|---|
| F | 0-600°C |
| G | 0-800°C |
| H | -50-+100°C |
| I | -100-+100°C |
| J | -100-+600°C |
| P3 | Dial switch -50-50/100/200/400°C |
| CODE | Output Signal Range |
|---|---|
| N | None |
| C | 0-20 mA |
| D | 4-20 mA |
| 3 | 0-5 V |
| 4 | 0-10 V |
| 5 | 1-5 V |
| 6 | 2-10 V |
| If you choose to purchase one output type, please enter "N" in column 2 of the output signal field. | |
| CODE | Working Power Supply |
|---|---|
| ADH | AC 85-264V DC 100-300V |
| ADL | AC/DC 20-56V |
| CODE | Selection Function |
|---|---|
| 01 | DC accuracy 0.1% |
| DP | Output signal switching DIP switch |


Technical documents