Display-type multi-functional signal isolation transmitter (one-to-one/one-to-two/one-to-three)
This display-type multi-functional signal isolation transmitter supports various types of inputs and outputs, features high precision, high-speed sampling, and RS-485 communication capabilities, and is suitable for industrial processes that require signal conversion, isolation, display, and communication integration.

Product Introduction
This series of transmitters features a three-color LCD display screen, providing intuitive visualization of input and output values. It integrates an 18-bit A/D input and a 15-bit D/A output, with a fast sampling rate of approximately 200 milliseconds. Inputs support various formats including thermocouples, RTDs, mA, and voltage (V/mV). Outputs are configurable as 4-20 mA, 0-20 mA, 0-10 V, 0-5 V, 1-5 V, and 2-10 V, and RS-485/Modbus RTU communication is optional. The product features a password lockout function, sensor disconnection detection, and a fully isolated design (power supply, input, and output are all isolated) to ensure process safety and signal stability.
- Dimensions: 22.5 × 96 × 83 (W*H*D) (mm)
- Installation method: Rail fixing
Product Features
- High-quality three-color LCD display screen.
- 18-bit A/D high-precision input.
- 15-bit linear D/A analog output.
- Supports 1-to-1, 1-to-2, and 1-to-3 analog output.
- 200 msec fast sampling speed.
- Supports DI digital input.
- Input, output, and power supply isolation design.
- Two-way setting menu.
- Displays the input value and the output percentage.
- Sensor disconnection detection function.
- The combination lock is set for protection.
- It has a simulated output testing function.
- It is compatible with multiple signal inputs, including Thermocouple, RTD, mA, and Voltage.
Selected model/specification: OWX-A-Code 1-Code 2-Code 3-Code 4-Code 5
| Code 1 | Working Power Supply |
|---|---|
| F | AC 90-250V |
| D | DC 11-40V |
| Code 2 | Analog Output 1 |
|---|---|
| A | Isolation 4-20 mA/0-20 mA |
| V | Isolation 0-10V/0-5V/1-5V/2-10V |
| N | None |
| Code 3 | Analog Output 2 |
|---|---|
| A | Isolation 4-20 mA/0-20 mA |
| V | Isolation 0-10V/0-5V/1-5V/2-10V |
| N | None |
| Code 4 | Analog Output 3 |
|---|---|
| A | Isolation 4-20 mA/0-20 mA |
| V | Isolation 0-10V/0-5V/1-5V/2-10V |
| D | DC 20V |
| N | None |
| Code 5 | Optional |
|---|---|
| 1 | DI Function |
| 2 | RS485 Modbus RTU |
| N | None |
Specifications
Power Supply and Basic Specifications
- Operating power supply: AC 90–250V 47–63 Hz、DC 11–40V
- Power consumption: 8 VA (4W maximum)
- Sampling rate: 5 times/second
- A/D resolution: 18 bits
- Display: Tri-color LCD (dual-zone display)
- Display text height: Top 8 mm white, bottom 6.5 mm green
Product Features
Signal Input Specifications
Supports multiple Thermocouple, RTD, mA, and Voltage formats:
| Type | Measurement Range | Accuracy | Input Impedance |
|---|---|---|---|
| K | -200~1370°C | ±2°C | 2.2MΩ |
| T | -250~400°C | ±2°C | 2.2MΩ |
| E | -100~900°C | ±2°C | 2.2MΩ |
| B | 0~1800°C | ±2°C | 2.2MΩ |
| R | 0~1767.8°C | ±2°C | 2.2MΩ |
| S | 0~1767.8°C | ±2°C | 2.2MΩ |
| N | -250~1300°C | ±2°C | 2.2MΩ |
| L | -200~900°C | ±2°C | 2.2MΩ |
| PT100 DIN | -200~600°C | ±0.4°C | 70.5Ω |
| PT100 JIS | -210~700°C | ±0.4°C | 650KΩ |
| mV | -8~70 mV | ±0.05% | 2.2MΩ |
| mA | -3~27 mA | ±0.05% | 1.3KΩ |
| V | -1.3~11.5 V | ±0.05% | 2.2MΩ |
Sensor Disconnection Detection
- TC/RTD/mV: Displays OPEN when open circuit
- 4–20 mA: less than 1 mA
- 1–5 V: below 0.25 V
- Response time: Approximately 4 seconds for TC/RTD/mV; approximately 0.1 seconds for 1–5V/4–20mA.
Analog Output
- Current output: 4–20 mA, 0–20 mA
- Voltage output: 0–5V, 1–5V, 0–10V, 2–10V
- Output resolution: 15 bits
- When stability reaches 99.9%, set the time to 0.1 seconds.
- Load capacity: Maximum current 500Ω, minimum voltage 10KΩ
- Isolation withstand voltage: 1000 VAC
Communication Function
- Interface: RS-485 Modbus RTU
- Speed: 2.8Kbps~38.4Kbps
- Address: 1~247
- Data bits: 7 or 8
- Check bits: None, Even, Odd
- Stop bits: 1 or 2
- Communication memory: 160 bytes
Physical and Environmental Specifications
- Shell material: Flame-retardant polycarbonate
- Dimensions: 22.5 × 96 × 83 mm
- Installation method: Rail fixing
- Operating temperature: -10~50°C
- Storage temperature: -40~60°C
- Humidity: 0–90% RH (non-condensing)
- Height restriction: 2000 meters
- Insulation resistance: minimum 20 MΩ (500VDC)
- Withstand voltage: 2000 VAC for 1 minute
- Earthquake resistance: 10 m/s (two hours)
- Impact resistance: 20g
- Protection rating: Panel IP66, Housing/Terminals IP20
- Weight: 160 g
- Safety standards: UL61010C-1, CSA C22.2, EN61010C-1
Application Cases
- Conversion and isolation of various sensor signals (thermocouples, RTDs, mV/V, mA) in industrial processes.
- Data from the manufacturing equipment temperature monitoring and heating/cooling systems is transmitted to the PLC/DCS.
- The signal is connected in series with RS-485/Modbus RTU to communicate with the host computer or SCADA monitoring system.
- Integrated application of equipment maintenance, quality control and process data recording.


Technical documents